If you are in search of part numbers like 6011920-011, AM2-Z607-1, AM2-Z607-1W, and others that fall under the NSN 5925-01-383-1463, we have you covered with the catalog and procurement resources provided on this page. At the top of the page, you will be able to review a number of details and data that pertain to this particular NSN, while available offerings are listed out below. If any items on our NSN 5925-01-383-1463 catalog interest you, be sure to request a quote from our staff at your earliest convenience. You can do this by submitting a Request for Quote (RFQ) form through our website or by getting in touch with our team via phone or email.
As an ASAP Semiconductor platform operating with quality as a focus, all NSN 5925-01-383-1463 parts we stock come from trusted manufacturers and undergo any necessary inspections or testing prior to shipment. Additionally, every purchase you make will come delivered with all applicable qualifying certifications or manufacturing trace documentation. Aside from such commitments, we also strive to provide customers procurement solutions that equally balance competitive pricing and timely fulfillment. With so much to offer, choose ASAP MilSTD for NSN 5925-01-383-1463 supplies and more.
Item Name | Circuit Breaker |
Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
Federal Supply Class (FSC) | 5925 Circuit Breakers |
National Item Identification Number (NIIN) | 01-383-1463 (013831463) |
NCB Code | USA (01) |
Manufacturer | Bae Systems Information, Eaton Corporation, Heinemann Electric Co Inc |
Part Number | Manufacturer | Item Name | Cage Code | RFQ |
---|---|---|---|---|
6011920-011 | bae systems information | circuit breaker | 12436 | RFQ |
AM2-Z607-1 | eaton corporation | circuit breaker | 74193 | RFQ |
AM2-Z607-1W | eaton corporation | circuit breaker | 89946 | RFQ |
AM2-Z607-1W | heinemann electric co inc | circuit breaker | l3330 | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAT | BODY WIDTH | 1.480 INCHES MINIMUM AND 1.520 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.409 INCHES MINIMUM AND 2.533 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 200 PCT AND 11.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CTJS | UNPACKAGED UNIT WEIGHT | 6.500 OUNCES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
Relevant Components for NSN - 5925-01-383-1463, 5925013831463 | ||||
5930-01-558-3633 (5930015583633) | 5998-01-464-6151 (5998014646151) | 5935-01-506-9572 (5935015069572) | 5910-01-007-5962 (5910010075962) | |
5962-01-085-4176 (5962010854176) | 5905-01-416-9093 (5905014169093) | 5935-01-682-9240 (5935016829240) | 5950-00-193-8677 (5950001938677) | |
5950-01-127-8658 (5950011278658) | 5930-01-201-1993 (5930012011993) | 5998-00-153-4334 (5998001534334) | 5910-00-816-3875 (5910008163875) | |