Thank you for taking an interest in the various military and defense parts, aerospace parts, and other items that we offer. You have reached the RFQ page for part number CM-21A, a 3M Company item with the NSN 6665015302725 that is listed alongside the description “Alarm Gas Automatic.” If you are interested in part number CM-21A and wish to learn more about your purchasing options, be sure to submit the form below at your earliest convenience while supplying us with important information concerning your needs and restrictions alike. Once we have a chance to receive and review your completed form, a member of our staff will reach out to you in 15 minutes or less to present a tailored solution for your comparisons.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that shopping with us is as simple as possible, we make it easy to identify and procure exact items by listing parts alongside all applicable designations and information. For example, part number CM-21A is specifically listed with the NSN 6665-01-530-2725, and this code can be used to determine that it falls under FSC 6665 Hazard Detecting Instruments And Apparatus. Additionally, while tracing back to 3M Company, this NSN part was specifically produced under CAGE Code 76381. With our services and dedication to simple procurement in mind, get started with us today!
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |